Water disinfection with ozone, copper and silver ions, and temperature increase to control Legionella: seven years of experience in a university teaching hospital

Détails

ID Serval
serval:BIB_3B04574D5A16
Type
Article: article d'un périodique ou d'un magazine.
Collection
Publications
Institution
Titre
Water disinfection with ozone, copper and silver ions, and temperature increase to control Legionella: seven years of experience in a university teaching hospital
Périodique
Journal of Hospital Infection
Auteur⸱e⸱s
Blanc  D. S., Carrara  P., Zanetti  G., Francioli  P.
ISSN
0195-6701
Statut éditorial
Publié
Date de publication
05/2005
Peer-reviewed
Oui
Volume
60
Numéro
1
Pages
69-72
Notes
Comparative Study
Evaluation Studies
Journal Article --- Old month value: May
Résumé
The efficacy of ozonation, copper-silver ionization and increased temperature in controlling Legionella spp. in the hot water distribution networks of a university hospital was evaluated. Two separate water distribution networks were studied; network 1 which supplies the surgical intensive care units, and network 2 which supplies the medical intensive care units and the emergency room. Network 1 has been disinfected by ozonation since 1995, and network 2 has been disinfected by ionisation since 1999. The hot water temperature was increased from 50 to 65 degrees C in 1998 and 2000 in networks 1 and 2, respectively. Water samples and swabs of the water outlets were cultured for Legionella spp. between four and six times each year, providing data before and after implementation of the disinfection procedures. There was no significant difference in the proportion of samples positive for Legionella spp. after ozonation in network 1 or after ionization in network 2. In both networks, there was a significant reduction in legionella isolates after increasing the hot water temperature to 65 degrees C. Maintaining the hot water temperature above 50 degrees C throughout both networks proved to be the most effective control measure in our hospital.
Mots-clé
*Copper Disinfection/instrumentation/*methods/standards Environmental Monitoring Heating/*methods/standards Hospitals, University Humans Infection Control/methods/standards Ions Legionella pneumophila/*growth & development/isolation & purification Maintenance and Engineering, Hospital *Ozone Sanitary Engineering *Silver Switzerland Temperature *Water Microbiology Water Purification/instrumentation/*methods/standards